kW vs kVA: what is the difference?
kW (kilowatts) is the real power your equipment uses. kVA (kilovolt-amperes) is the apparent power a circuit delivers, calculated from volts times amps. kW equals kVA times the power factor.
Also called: kVA, kilovolt-ampere, MVA, megavolt-ampere
How it works
Circuits are rated in volts and amps, so their capacity comes out in kVA. A single-phase circuit delivers volts times amps. A three-phase circuit delivers volts times amps times 1.732. A 208V, 30A three-phase circuit works out to about 10.8 kVA.
Modern server power supplies run at a power factor close to 1, so kW and kVA end up close. Older or mixed equipment can sit lower, which means you get fewer usable kilowatts from the same circuit.
At the building level, the same idea scales up. Utility services, transformers and generators are often rated in MVA (megavolt-amperes), where 1 MVA is 1,000 kVA. A utility feed rated in MVA delivers fewer MW of real power once the power factor is applied.
There's one more step. Under the US National Electrical Code, breakers on continuous loads are sized at 125% of the load, which means you plan to use no more than 80% of a standard breaker's rating. That 10.8 kVA circuit gives you about 8.6 kVA to work with.
Why it matters when you buy
Providers quote power in different units. One quote says 10 kW, another says a 30A circuit, a third says 8 kVA. Convert them all to usable kW before you compare prices, or you'll compare different amounts of power.
What to ask the provider
- Is my power commitment in kW or kVA, and is it the breaker rating or usable capacity?
- What voltage and phase are the circuits?
- Are the breakers standard (80%) or 100% rated?
Source: IAEI Magazine, "100% vs. 80%: Choosing the right OCPD solution" (NEC 210.20(A))