How it works
The two feeds share your load while both are up. When one drops, the other has to carry everything. That means the total load across both feeds must fit within what a single feed can deliver, after the 80% continuous-load limit.
This is the most common power mistake in colocation. A rack with two 30A feeds doesn't have 60A to use. It has the capacity of one 30A feed, and a team that loads both sides close to the limit will trip the surviving breaker during the exact failure A+B power was meant to cover.
Why it matters when you buy
A+B power only protects you if your load is sized for failover and your equipment has dual power supplies. Some providers bill A+B as two circuits but cap your usable power at one. Make sure the price, the commitment and the failover math all line up.
What to ask the provider
- Are the A and B feeds from separate UPS systems and separate distribution?
- Am I billed for both circuits or for the usable capacity of one?
- Do you alert me when my combined load passes what one feed can carry?