A/B Redundant Power Calculator: Can One Feed Carry the Load?

Redundant A and B feeds only protect you if either one can carry the full load alone. Enter what each feed draws today and see the load on the survivor if the other trips. Three-phase circuits are checked leg by leg.

Last verified November 22, 2026

1 safe0 warning1 criticalTotal load 9.15 kW
Safe
Phase
Feed A amps
Feed B amps
Feed A 30%Feed B 27%If one feed fails 57%Load 3.54 kW
Critical
Phase
Feed A amps
Feed B amps
Feed A 47%Feed B 43%If one feed fails 90%Load 5.62 kW

Why A and B power fails in practice

Redundant A and B feeds are meant to keep a rack running when one feed is lost for maintenance or a fault. They only work if the surviving feed can carry the whole load. The most common mistake is to watch each feed on its own. Two feeds at 45% each look healthy, but if one fails the other jumps to 90%, past the 80% continuous limit, and its breaker can trip. A fully redundant rack then goes dark.

Worked example: one safe rack, one critical

The calculator opens with two racks on 208V 30A single-phase pairs. Rack 1 draws 9A on A and 8A on B. Each feed is under a third of its breaker, and if one fails the survivor carries 17A, or 57% of 30A. That is safe, and the rack is drawing about 3.5 kW.

Rack 2 draws 14A and 13A. Each feed looks fine at 47% and 43%, but the combined 27A is 90% of the breaker. If either feed fails, the other is overloaded. That rack is critical at about 5.6 kW, even though neither feed looks busy on its own.

How to read the thresholds

The check uses the same 80% continuous limit that sets usable power. Safe means the combined load is at or below 70% of one breaker and each feed is at or below 75%, which leaves room for peaks. Warning means you are close. Critical means a single feed failure would push the survivor past 80%. For three-phase circuits, each leg is checked on its own, because the busiest leg trips first.

What to do about a critical rack

Move some devices to another rack or circuit, balance three-phase loads across legs, retire idle gear, or upgrade the circuit. The same 30A breaker in three-phase carries about 1.7 times the power. Single-corded devices are only as redundant as the circuit they plug into, so put them on a rack transfer switch fed by both A and B, or accept the risk in writing.

Where to get good readings

Use peak amps from metered PDUs or the provider's power report, not nameplate ratings or one-off readings. Check after adding equipment and before planned maintenance, when one feed will be taken down on purpose.

Three-phase example: balanced enough?

Take a 208V 30A three-phase pair drawing 10, 11 and 9 amps on the A feed legs and 9, 10 and 8 on the B feed legs. Each feed peaks at 11A, about 37% of the breaker. If one feed fails, the busiest leg carries 21A, exactly 70% of 30A, so the rack is just inside the safe band at about 6.8 kW.

The legs are not even, though. Combined, they carry 19, 21 and 17 amps, a spread of about 21% around the average, which the calculator flags. Moving one device from the second leg to the third would bring the busiest leg down and buy headroom without touching the breaker.

How it's calculated

  • Feed load = feed amps ÷ breaker size
  • Failover load = (feed A amps + feed B amps) ÷ breaker size
  • Safe: each feed at or below 75% and failover at or below 70%
  • Warning: a feed above 75% or failover above 70%
  • Critical: a feed or failover above 80%
  • Three-phase circuits are checked leg by leg (L1, L2, L3); the busiest leg sets the limit
  • Phase imbalance = (highest leg − lowest leg) ÷ average leg, flagged above 20%

Estimates for planning, not a quote. Contract terms and provider billing rules vary.

Common questions

Why does failover matter more than each feed?

When one feed fails, the other picks up its load. If the combined load is over 80% of the breaker, the surviving circuit can trip and take the rack down.

What should I do if a circuit is critical?

Move load to another circuit, rebalance across racks or upgrade the circuit. A three-phase circuit at the same amperage carries about 1.7 times the power.

Where do I get the amp readings?

From your PDU display or monitoring, or ask your provider for a power report. Use peak readings, not averages.

What percentage should each A and B feed run at?

With the load split evenly, keep each feed at or below about 40% of its breaker, so the survivor stays at or below 80% if one fails.