Colocation Cost Calculator: Flat vs. Metered Power

Flat pricing bundles power into one rate per kW. Metered pricing charges a lower base rate plus the energy you draw. Which is cheaper depends on how much of your commitment you really use.

Last verified November 22, 2026

Flat (all-in) pricing

Metered pricing

Flat monthly$2,250
Metered monthly$1,7264,380 kWh billed a month
Metered saves$524/mo$6,293 a year
Break-even utilizationn/aAbove this, flat pricing wins

How flat and metered colocation pricing work

Flat or all-in pricing charges one rate per committed kW each month, whatever you draw. Metered pricing charges a lower base rate per committed kW for space and capacity, then bills the energy you use per kWh. Flat pricing buys predictability. Metered pricing rewards running well below your commitment and penalizes running close to it.

Worked example: 10 kW at 60% utilization

The calculator opens with 10 kW committed. Flat at $225 per kW is $2,250 a month. Metered at a $120 base is $1,200, plus energy: 10 kW × 60% × 730 hours = 4,380 kWh at $0.12, or about $526, for a total of about $1,726. Metered saves about $524 a month here. At these rates the break-even is above 100% utilization, so metered wins at any draw.

Now set the PUE multiplier to 1.4, which some providers use to recover cooling energy. Billed energy rises to 6,132 kWh and metered rises to about $1,936. The break-even drops to about 86% utilization. Above that, flat pricing would be cheaper. The PUE term is the line to read most carefully in a metered quote.

The break-even formula

Metered costs the same as flat when base rate + utilization × 730 × energy rate × PUE = flat rate. Solving for utilization gives (flat rate − base rate) ÷ (energy rate × 730 × PUE). Below that utilization, metered is cheaper. Above it, flat is cheaper.

What providers bill differently

Some metered quotes pass through the utility rate and change it when the utility does. Others charge a fixed rate with a markup. Some multiply your kWh by a PUE factor, fixed or measured. Some bill energy on the peak draw rather than the average. Flat quotes can still carry overage charges if you exceed your commitment. Ask how energy is measured, how often the rate can change and whether a cooling factor applies.

Which should you choose?

Use your measured average utilization from today's site, not the circuit size. If you average well below your commitment, metered usually wins. If you run close to it, or you need a fixed budget, flat is simpler. Either way, compare the full quotes with our quote comparison calculator, which adds the term, escalators, cross connects and fees.

How utilization changes the answer

Keep the default rates and change only utilization. At 40%, metered costs about $1,550 a month. At 80%, about $1,901. Flat stays at $2,250 either way, so with a pass-through energy rate metered is cheaper across the range.

Add a PUE multiplier of 1.4 and the picture changes. At 90% utilization, metered rises to about $2,304, now more than flat. The same quote can be the cheaper option or the more expensive one depending on how hard you run your racks and how the provider bills cooling, so test your real utilization, not a guess.

How it's calculated

  • Flat monthly = committed kW × flat rate
  • Metered energy = committed kW × utilization × 730 hours a month
  • Metered monthly = committed kW × base rate + energy kWh × energy rate
  • If the provider bills cooling through PUE, energy kWh is multiplied by the PUE you enter
  • Break-even utilization = (flat rate − base rate) ÷ (energy rate × 730 × PUE)

Estimates for planning, not a quote. Contract terms and provider billing rules vary.

Common questions

Which is cheaper, flat or metered colocation power?

Metered usually wins when you draw well below your commitment. Flat wins when you run close to it, because you pay one predictable rate.

Does the energy rate include cooling?

Ask. Some providers multiply metered kWh by a PUE factor to recover cooling energy, which raises the effective rate.

What utilization should I assume?

Use measured averages from your current site if you have them. Most enterprise racks average well below their circuit capacity.

What is PUE billing in colocation?

Some providers multiply your metered kWh by a power usage effectiveness factor, such as 1.4, to recover the energy used for cooling. It raises the effective energy rate by that factor.

Is my data sent anywhere?