Single-phase vs. three-phase power: what is the difference?
Single-phase power uses one alternating current, while three-phase power uses three currents offset from each other. At the same voltage and amps, a three-phase circuit delivers about 1.73 times as much power, which is why dense racks use it.
Also called: single-phase power, 3-phase power, three-phase power, 208V three-phase
How it works
A single-phase circuit's capacity is volts times amps. A three-phase circuit's capacity is volts times amps times 1.732. A 208V, 30A single-phase circuit delivers about 6.2 kVA, while a 208V, 30A three-phase circuit delivers about 10.8 kVA, before the 80% continuous-load limit.
In US data centers, 208V service is common for racks, delivered as either single-phase or three-phase circuits. Higher-density deployments increasingly use 415V three-phase, which carries more power over the same size wire.
Why it matters when you buy
Three-phase circuits need rack PDUs built for three-phase, and the load should be balanced across the phases so no one phase trips first. If your racks will draw more than a single-phase circuit can carry, ask for three-phase from the start. Changing later usually means new circuits and new PDUs.
What to ask the provider
- What voltages and phases do you offer for rack circuits?
- Do you monitor phase balance on three-phase circuits?
- What does it cost to move from single-phase to three-phase later?