Rack Elevation Template (Free Excel and PDF)
A rack elevation diagram you can fill in. The Excel version draws the front and rear views from a device list and checks U conflicts, weight and whether one power feed can carry the rack. The PDF gives you blank 42U and 48U elevations to print for site surveys and move day.
Last verified November 22, 2026
What's in the rack elevation template
- An Excel rack sheet you copy once per rack, with front and rear views drawn from a device list
- Automatic checks for U conflicts, devices above the top of the rack, total weight against the rack rating and load on one feed if the other fails
- Device type colors for network, server, storage, power, cabling and blanking
- A filled-in 42U example rack
- A printable PDF with ten things to get right, blank 42U and 48U elevations, a row layout page and an install sign-off
Worked example: the sample 42U rack
The Example Rack sheet holds 16 items: patch panels, two top-of-rack switches, two firewalls, four servers, a storage array, a backup appliance, blanking panels and a shelf. They use 27 of the 42 rack units, leaving 15 free.
The equipment weighs 434 pounds. Add the 300-pound empty rack and the total is 734 pounds, about 24% of a 3,000-pound static rating. Measured load is 5.45 kW on a 208V 30A three-phase A and B pair. One such circuit is about 10.8 kW at full rating, so if either feed fails, the other carries about 50% of its rating. That is inside the 70% comfort zone, with room to add gear. The same rack on a single-phase 208V 30A pair, at 6.24 kW per circuit, would sit at about 87%, which the sheet flags as critical.
How to keep an elevation accurate
Make the elevation part of every change ticket, so nobody adds, moves or removes a device without updating it. Spot-check a few racks against their drawings each quarter. Keep one copy in a shared location rather than versions on laptops, and print a fresh copy for move day. Label each device with the rack ID and U position so the drawing and the rack always agree.
Rack elevation mistakes that cause trouble on move day
Front view only
Rear-mounted switches, PDUs and managers drop off the drawing and get missed in a move.
Airflow not recorded
A switch installed backward exhausts into the cold aisle.
Missing blanking panels
Empty U left open lets hot air recirculate, and panels vanish during moves.
Guessed weights
Estimates put racks over the rack or floor rating. Use spec sheets or a scale.
Adding A and B feeds together
With redundant power the whole rack must fit on one circuit if the other fails.
A stale drawing
Once the elevation drifts from the rack, nobody trusts it. Update it with every change.
The PDF covers each of these in full.
About this rack elevation template
A rack elevation is a drawing of a rack, front and rear, that shows what sits in every rack unit. Good ones also record airflow direction, the PDU outlets each power supply uses, weight and power. Colocation buyers use them to plan a cage, order the right circuits, brief remote hands and rebuild racks exactly after a migration.
We built this template after reviewing published rack elevation guides, rack handbooks and spreadsheet examples. The Excel workbook counts rack units from U1 at the bottom, supports racks up to 52U, flags two devices in the same U, color-codes gear by type and checks measured load against one circuit's breaker rating, the same test our A/B circuit calculator uses.
How to use the rack elevation template
- Download the Excel template and copy the Rack Elevation sheet once per rack.
- Enter the rack details and circuit size, then list every device with its bottom U, height, mount face, type, watts and weight.
- Fix anything flagged as a conflict, above the rack or over the power threshold.
- Print the elevation, or the blank PDF pages, for site surveys, remote hands tickets and move day sign-off.
A planning template. Confirm floor ratings, circuit sizes and equipment weights with your provider and equipment vendors.
Common questions
What is a rack elevation diagram?
A front and rear drawing of a rack that shows which device sits in each rack unit, with details such as airflow direction, power connections and weight. It is used to plan, document and rebuild racks.
How tall is one rack unit?
One rack unit (1U) is 1.75 inches, or 44.45 mm. A 42U rack has 42 mounting positions, numbered from U1 at the bottom.
Should a rack elevation show the front and rear?
Yes. Many switches, PDUs and cable managers mount on the rear, and full-depth servers use both faces. A front-only drawing misses them.
How much power can a rack with A and B circuits use?
Plan to one circuit. If either feed fails, the other must carry the full load, so keep measured load at or below 80% of one circuit's breaker rating.
Can I make a rack elevation in Excel?
Yes. List each device with its bottom U and height, and let formulas draw the front and rear views. This template does that and adds weight and power checks.