A colocation quote is a price proposal that lists monthly recurring charges for space, power, cross connects, bandwidth and support, plus one-time setup fees and contract terms. To read one well, convert everything to cost per usable kW and total cost over the term, then check the escalator, renewal and exit terms before you sign.
That sounds simple. Then the PDF arrives with eleven line items, three acronyms nobody defined and a footnote in a font size normally reserved for prescription side effects. This guide walks through every part of a typical quote, what each line really means and where the money hides.
| Quote line item | What it means | What to watch for |
|---|---|---|
| Space | Rack, half rack, cage or square feet | A low space price paired with expensive power |
| Power | Circuits by voltage and amps, or a kW commitment | Both A and B circuits billed at full price |
| Metered power | Usage billed per kWh above a base | Overage rates and utility pass-throughs |
| Cross connects | Monthly fee per physical connection to a carrier or partner | Per-connection fees that escalate every year |
| IP and bandwidth | Addresses and internet transit, if bought from the facility | Commit levels and burst charges |
| Remote hands | Hourly or bundled onsite help | Minimums, rounding and after-hours rates |
| One-time charges (NRCs) | Install, setup, cage build and circuit install | Fees not quoted until the contract stage |
| Taxes and fees | Sales tax, regulatory or admin fees | Lines that say "taxes not included" |
| Terms | Length, escalator, renewal and exit | Auto-renewal and short notice windows |
What is in a colocation quote?
Every colocation quote is built from the same handful of parts. The order and labels change from provider to provider, which is half the reason comparing them feels like assembling furniture from three different sets of instructions.
Space
Space is usually quoted as a full rack, a half rack, a private cage or, for larger deployments, square feet. A full rack price often includes the cabinet itself. A cage price may or may not include the cabinets inside it, so check before you assume.
Cross connects
A cross connect is a physical cable between your equipment and a carrier, cloud on-ramp or another customer in the same building. It is billed monthly per connection. In the quotes we see, cross connects typically run about $100 to $450 per connection per month. A $0 cross connect exists but is rare enough to deserve a photo.
IP addresses and bandwidth
Some facilities sell internet transit and IP address blocks directly. Others expect you to bring your own carrier. If bandwidth is on the quote, check the commit level, burst pricing and whether it is a blended service. Our data center connectivity options guide covers carrier choices in more detail.
Remote hands
Remote hands is onsite help from facility staff, such as rebooting a server, swapping a drive or checking a cable. In the quotes we see, it is billed hourly or in bundled hours, usually about $100 to $250 per hour. Some smaller providers include a set amount of remote hands with certain colocation services. See our remote hands vs smart hands guide for what those services cover.
One-time charges
Nonrecurring charges (NRCs) are one-time fees for installation, setup, cage builds and circuit installs. They are easy to overlook because they are not part of the monthly number. They also tend to be the first place a salesperson finds room to negotiate.
Taxes and fees
Many quotes say "plus applicable taxes" and stop there. Sales tax treatment of colocation varies by state, and some programs that exempt data center equipment were written with large developers in mind. Our data center tax incentives guide covers the state rules. Ask for an estimate of taxes and any regulatory or admin fees in writing.
How is power priced in a colocation quote?
Power is usually the largest line on a colocation quote and the hardest to compare. Providers price it in a few different ways.
Breakered, metered or all-in
A breakered circuit is a flat monthly fee for a circuit of a given size, no matter if you draw 10% or 80% of it. Metered power charges a rate per kWh for what you actually use, sometimes on top of a base fee. All-in pricing bundles space, power and cooling into one rate per kW. In current quotes we see, retail all-in pricing runs about $215 to $280 per kW per month, which makes a useful sanity check for any quote. Our colocation pricing guide explains the models in depth.
The 80% rule
Electrical code practice limits continuous load to 80% of a circuit's breaker rating. A 30A 208V single-phase circuit has 6.24 kW of nameplate capacity but about 4.99 kW of usable continuous load. When you compare quotes, divide the monthly price by usable kW, not nameplate kW. Our rack power guide walks through the math for other circuit sizes.
A and B circuits
A and B circuits give each device two independent power feeds. The B side is there for failover, so your total draw across both should stay within the safe limit of one circuit. The B circuit does not add usable capacity. Some quotes still price the B circuit at the full rate of the A circuit, which means you pay twice for one circuit's worth of usable power. Others discount the redundant circuit. Ask which one you are looking at.
Which contract terms in a colocation quote matter most?
The price on page one is only half the story. The terms decide what that price becomes in year three.
Term length and escalators
Longer terms can earn a lower starting rate. The annual escalator then raises it every year. JLL's midyear 2026 North America data center report said most leases signed today carry annual escalations of 3% or more. In the contracts we reviewed for an earlier guide, one small provider allowed CPI plus 2% after the first year, plus increases tied to electricity costs at any time. Escalators often live on the service order rather than the master agreement, so read both. To see what an escalator adds over the full term, run the quote through our colocation TCV calculator.
Auto-renewal and notice windows
In the standard agreements we reviewed, service orders commonly auto-renewed for 12 months unless you gave written notice 30 days before the term ended. In one major provider's form, the provider could send new renewal pricing inside that window. Notice often has to go by mail or courier, not email. Put the date on your calendar the day you sign.
Ramp schedules
A ramp lets you start with less space or power and grow into the full commitment on a set schedule. It is useful when you are migrating in phases. Check that the billing ramp matches your real move dates and that unused capacity is not billed at the full rate from day one.
Early termination
In one major provider's standard agreement, early termination for convenience cost 100% of the remaining monthly recurring charges for the rest of the term. Only one agreement we read reduced that fee if the provider re-licensed the space. Ask for a declining fee or a mitigation clause before you sign.
Quote expiration and pass-throughs
Most quotes carry an expiration date, after which pricing is no longer guaranteed. Note it the day the quote arrives. Also look for utility adjustment or power pass-through clauses that let the provider raise power rates when its own costs rise. Commercial electricity prices vary widely by state. The EIA's state electricity price table put the August 2026 commercial average at 14.47 cents per kWh nationally, up from 13.87 cents a year earlier. The same table ranged from about 8 cents in North Dakota to about 30 cents in California.
Deposits and credit checks
Providers may run a credit check and ask for a deposit, prepayment or letter of credit, especially for newer companies. Ask how much, when it is refunded and if it can be applied to future invoices.
What should you watch out for in a colocation quote?
This is the part of the quote where "competitive pricing" goes to have a quiet word with your budget.
Cheap space with expensive power
A quote with a low rack price can still be the most expensive offer if the power is priced high. Always add space and power together and divide by usable kW. A $300 rack with $1,500 of power is not cheaper than a $1,300 rack with power included.
Both circuits billed at full
As covered above, paying full price for A and B circuits doubles your power cost without doubling capacity. Look for separate line items with the same price.
Metered overage rates
Metered and committed-kW quotes often charge a higher rate for usage above the commitment. Ask for the overage rate in writing, how it is measured and if you get a warning before it applies.
Fees that grow
Cross connects and remote hands can escalate on their own schedule. Ask whether the escalator applies to every line or only space and power. Four cross connects at the top of the range can rival the cost of the rack.
Remote hands minimums and after-hours rates
Some providers bill a minimum block per ticket, round up to the next increment or charge a higher rate after hours and on weekends. A five-minute reboot at 2 a.m. can cost far more than five minutes.
Included or extra
Check what comes with the space. PDUs, shelves, locks, cage doors, access badges, monitoring and a parking spot can each be included or billed separately. If it is not on the quote, assume it costs money.
SLA credits and caps
Service credits are usually a percentage of the affected monthly charge, often capped and often described as the sole remedy. Credits typically must be claimed in writing within a short window. In one major provider's form it was 30 days after month end. Because a credit is a slice of one month's charge, it is usually small next to the real cost of an outage to your business. Liability caps of 12 months of fees were common in the agreements we read. Our colocation SLA template shows stronger credit terms to ask for.
Billing start dates
In one major provider's standard form, billing started after a short acceptance period even if the customer was not ready to move in. It could also start if power configuration details were not provided within 10 business days. Ask for a billing start tied to a written acceptance checklist.
Surprises at signing
Some charges appear only when the contract arrives. Shipping and receiving, storage, loading dock use, escorted access and installation labor are common examples. Ask for a complete list of possible fees before the contract stage.
How do you compare colocation quotes apples to apples?
Put every quote on the same basis. Our colocation RFQ template asks every provider for the same line items. First, normalize the monthly recurring charge to cost per usable kW. Then calculate the total cost over the full term, including escalators and one-time charges. Finally, compare the terms that do not show up in either number, such as renewal, exit and SLA language. Our free colocation quote comparison calculator does the first two steps for up to four quotes at once.
Illustrative colocation quote comparison
This is an illustrative example with made-up round numbers, not real pricing. Both quotes are for one rack with A and B 30A 208V circuits, about 4.99 kW usable, two cross connects and a 36-month term.
| Line item | Quote A | Quote B |
|---|---|---|
| Rack space | $300 | $1,300 all-in with power |
| A circuit | $750 | Included |
| B circuit | $750 | Included |
| Two cross connects | $600 | $400 |
| Monthly total | $2,400 | $1,700 |
| Cost per usable kW per month | about $481 | about $341 |
| Annual escalator | 4% | 3% |
| One-time charges | $1,000 | $2,500 |
| Total over 36 months | about $90,900 | about $65,550 |
Quote A looks cheaper on space and on setup fees. Over three years it costs about $25,000 more, mostly because both circuits are billed at full price. That is the kind of difference a sticker comparison never shows.
What questions should you ask about a colocation quote?
- What is the usable kW for each circuit, and is the B circuit billed at the full rate?
- Which lines does the escalator apply to, and is it fixed or tied to CPI?
- Is there a power pass-through or utility adjustment clause?
- When does billing start, and what does acceptance require?
- What are the renewal term, notice window and notice method?
- What does early termination cost, and does it decline over time?
- What are the remote hands minimums, rounding and after-hours rates?
- What is included with the space, and what is billed separately?
- What do SLA credits pay, how are they claimed and what is the cap?
- What fees could appear at contract that are not on this quote?
- How long is this quote valid?
What are the red flags in a colocation quote?
- No usable kW or circuit details, just "power included".
- An escalator that applies to everything with no cap.
- Renewal price increases that can arrive inside the notice window.
- Early termination equal to every remaining month, paid before you can remove equipment.
- Vague lines such as "fees as applicable" or "standard rates apply".
- A quote that expires in days with pressure to sign now.
- Reluctance to put verbal promises in writing.
None of these alone means walk away. Together they mean read slowly and ask a lot of questions.
What belongs on your colocation quote checklist?
- Confirm the space type, size and what comes with it.
- Write down usable kW for every circuit.
- Check whether the B circuit is billed at full price.
- Find the metered rate and overage rate.
- List every cross connect fee and its escalator.
- Note remote hands rates, minimums and after-hours pricing.
- Add up all one-time charges.
- Ask for taxes and fees in writing.
- Record the term, escalator, renewal and notice window.
- Read early termination and SLA terms.
- Check the quote expiration date.
- Normalize to cost per usable kW and total cost over the term.
- Compare offers side by side and get quotes from several providers.
Frequently asked questions about colocation quotes
How long is a colocation quote valid?
Most quotes include an expiration date printed on the quote. After that, pricing and availability can change, so confirm both before you sign.
Are colocation quotes negotiable?
Often, yes. One-time charges, escalators, renewal terms, cross connect fees and remote hands bundles are common places to negotiate, especially on longer terms.
What is an NRC on a colocation quote?
An NRC is a nonrecurring charge, a one-time fee for installation, setup, cage builds or circuit installs. Add it to the total cost over the term when comparing offers.
Why is power listed separately from space?
Power is the main cost driver for most deployments, so many providers price it separately by circuit, by committed kW or by metered usage.
Is A and B power billed twice?
Sometimes. The B circuit is for redundancy and does not add usable capacity, but some quotes bill it at the full rate. Ask before you sign.
What is a good price per kW?
In the quotes we see, retail all-in pricing runs about $215 to $280 per kW per month. Location, density, term and facility quality can all move that number.
More in Colocation Pricing and Contract Articles
Compare facilities: Retail colocation data centers
Comparing data centers?
Send us your requirements. We'll shortlist the providers that fit and get you pricing.